Author:
Yari Meysam,Kalbasi Rasool,Talebizadehsardari Pouyan
Abstract
Purpose
This study aims to simulate the flow and heat transfer through an air handling unit to reduce its energy consumption by a novel creative idea of using an air-to-air heat exchanger.
Design/methodology/approach
To do this, both first and second laws of thermodynamics energy and exergy balance equations were solved numerically by an appropriate developed computer code.
Findings
Using the air-to-air heat exchanger in dry conditions decreases the cooling coil load by 0.9 per cent, whereas the reduction for humid conditions is 27 per cent. Similarly, using air-to-air heat exchanger leads to an increase in the first law of efficiency in dry and humid conditions by 0.9 per cent and 36.8 per cent, respectively.
Originality/value
The second law of efficiency increases by 1.55 per cent and 2.77 per cent in dry and humid conditions, respectively. In other words, the effect of using an air-to-air heat exchanger in humid conditions is more than that in dry conditions.
Subject
Applied Mathematics,Computer Science Applications,Mechanical Engineering,Mechanics of Materials