Purpose
Good illumination creates an aesthetic environment that may positively influence patients’ well-being and provide comfort to the hospital staff. This study aims to focus on exploring the energy efficiency of lighting and subjective perception of the lit environment in a hospital ward to assess quality indicators of ambient lighting conditions.
Design/methodology/approach
The existing conventional tubular fluorescent lamp–based lighting system in the surveyed patients’ ward was retrofitted with light-emitting diode (LED) luminaires to explore illumination and energy parameters. Thereafter, a software lighting model was created, simulated and analyzed. A Web-based survey with five bipolar adjective pairs in a semantic differential scale was conducted with 48 participants to record and analyze their subjective responses pertaining to the variations in lamp types and surface reflectance combinations.
Findings
The findings imply that the LED tubular lamp–based illumination was deemed more adequate compared to other lamp types and the effects of variations in room surface reflectance combinations on the participants’ responses were statistically significant at α = 0.05 level. The simulated horizontal work plane average illuminance level varied from 131 to 171 lx, mean room surface exitance (MRSE) levels remained between 30 and 90 lm/m2 and overall uniformity of illuminance remained between 0.5 and 0.7.
Originality/value
In a hospital ward illuminated by LED tubular lamps, variations in room surface reflectance combinations for a constant luminous flux package output from the lamps may affect the subjective perception of users and the correlation between horizontal work plane average illuminance and MRSE is found to be highly linear (coefficient of determination > 0.97).
Subject
Building and Construction,Architecture,Human Factors and Ergonomics
Reference73 articles.
1. Syncing with the sky: daylight-driven circadian lighting design;LEUKOS,2020
2. Daylight for energy savings and psycho-physiological well-being in sustainable built environments;Journal of Sustainable Development,2008
3. Energy efficient lighting system design for hospitals diagnostic and treatment room – a case study;Journal of Light & Visual Environment,2012
4. On the efficiency of lighting by LEDs in visual work;Light & Engineering,2018
5. A human-centric approach to assess daylight in buildings for non-visual health potential, visual interest and gaze behavior;Building and Environment,2017
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献