Author:
Bao Qing,Wang Baojin,Li Manman,Li Chao,Gao Jin
Abstract
Purpose
A section of in-service PE gas pipeline in Guocun, Beijing, was found to appear gas leaking at the electrofusion (EF) joint. This study is dedicated to reveal the material cause of EF joint failure to help with a more accurate prediction of service life of PE gas pipe and further normalize the construction of PE gas pipeline.
Design/methodology/approach
Defect detection was carried out on the leaking EF joint using ultrasonic phased array. The mechanical degradation and structural aging behavior was studied by tension test, FTIR technology, TG test and DSC test. The organic components in the soil surrounding the PE gas pipe failure area were qualitatively identified.
Findings
The results showed that the organic surfactants in the soil environment could accelerate the aging behavior of PE material, leading to a deterioration of mechanical properties and a serious reduction in the ability of the PE pipe and EF joint, especially at the welding defect, to resist external force.
Originality/value
A novel study was conducted to investigate the failure cause of the EF joint of in-service PE gas pipe, incorporating the analysis of environmental factors and structural deterioration.