Author:
Timbury M. C.,Donaldson J. R.,McCartney A. C.,Fallon R. J.,Sleigh J. D.,Lyon D.,Orange G. V.,Baird D. R.,Winter J.,Wilson T. S.
Abstract
SUMMARYThe bacteriological investigation of an outbreak of Legionnaires' disease in Glasgow Royal Infirmary affecting 16 patients is described. Most of the patients had been treated in high-dependency areas on two floors of the hospital supplied by the same two air-conditioned ventilation systems. The source of infection was traced to contamination of a cooling tower from which a plume of spray discharged into the intake vents of the two ventilation systems. Rubber grommets within the cooling tower probably provided a nidus of infection there. The control and management of the outbreak are discussed: a policy of frankness about the course and progress of the investigations was adopted and helped to allay anxiety on the part of both staff and media.
Publisher
Cambridge University Press (CUP)
Subject
Public Health, Environmental and Occupational Health,Immunology
Cited by
39 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献