The Globe Thermometer in Studies of Heating and Ventilation

Author:

Bedford T.,Warner C. G.

Abstract

The effects of radiation and convection on the globe thermometer have been studied.Equations have been obtained, and alignment charts constructed, for the calculation of mean radiation intensity and of equivalent temperature from readings of the globe thermometer, air temperature and air velocity.The accuracy of these methods has been tested on observations made under industrial conditions. Taking direct thermopile observations as the standard, the mean radiation intensity values calculated from globe thermometer readings had an average error of 1·2 B.Th.U. per sq. ft. per hour. With eupatheoscope readings as standard, equivalent temperature estimates had a mean error of 1·2°.It is concluded that, while globe thermometer readings alone are unreliable as indications of the effects of the thermal environment, valuable results can be obtained by using the instrument along with an ordinary thermometer and a silvered kata-thermometer.

Publisher

Cambridge University Press (CUP)

Subject

Infectious Diseases,Epidemiology

Reference19 articles.

1. The measurement of radiant heat in relation to human comfort;Vernon;J. Physiol.,1930

2. The measurement, in relation to human comfort, of the radiation produced by various heating systems;Vernon;Proc. Inst. Heating and Vent. Eng.,1932

3. Building Research Board. Report for the Year 1931. Appendix I.

Cited by 101 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3