Abstract
SUMMARYTwelve patients in a large teaching hospital contracted Legionnaires' disease over a period of 11 months. The source was a domestic hot water system in one of the hospital blocks, which was run at a temperature of 43 °C. Five different subtypes ofLegionella pneumophilaserogroup 1 have been isolated from water in different parts of the hospital, over a period of time. Only one subtype, Benidorm RFLP 14, was implicated in disease. Circumstantial evidence suggested that the outbreak may have been due to recent colonization of the hot water system with a virulent strain ofLegionella pneumophila. The outbreak was controlled by raising the hot water temperature to 60 °C, but careful surveillance uncovered two further cases in the following 30 months. Persistent low numbers ofLegionella pneumophilawere isolated from the domestic hot water of wards where Legionnaires' disease had been contracted, until an electrolytic unit was installed releasing silver and copper ions into this supply.