Abstract
Indoor air pollution is complex and serious. In fact, an on-site investigation of an office building revealed that the concentration of three typical pollutants (CO2, VOCs, PM2.5) exceeded the Chinese standard. To identify a better control method to achieve good indoor air quality, an orthogonal experiment was carried out in an environmental chamber to compare the control time and energy consumption of four control methods (purifier+ and window+, purifier+ and window-, purified fresh air 240 m3/h and purified fresh air 400 m3/h) to meet the standard established for pollutants. The purifier+ and window+ method was found to be more effective in most conditions, with a control time reduced by 8.06% and energy consumption reduced by 11.91% compared with the traditional control method of purified fresh air 240 m3/h. This research highlights the optimal control strategy for the air quality in office buildings under different pollution conditions.
Funder
national key research and development program
Publisher
Public Library of Science (PLoS)
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献