Affiliation:
1. College of Sciences, Inner Mongolia University of Technology, Hohhot 010051, China
Abstract
Abstract
The effect of high voltage electrostatic field and high voltage alternating current electric field on the heat exchanger surface fouling under the conditions of hard water was investigated. The Ca2+ concentration in two water conditions was 12 mmol/L. The Mg2+ concentration was 10 mmol/L and 12 mmol/L respectively. The concentration changed with the Mg2+ concentration. X-ray diffraction and scanning electron microscope results confirmed that the main crystal phases of the scale samples consisted of calcite and aragonite. The high voltage electrostatic treatment can promote scale growth under both water quality conditions. However, the high voltage alternating current electric field treatment shows a good scale inhibition effect under both water quality conditions, and the scale inhibition effect is best when both Ca2+ and Mg2+ concentrations are 12 mmol/L, and the average scale inhibition rate reaches 47.58%. When the calcite content of the scale sample is significantly higher than that of aragonite, Mg2+ affects the growth and solubility of crystals. Conversely, the high voltage alternating current electric field treatment can effectively extend the fouling induction period of the adherent scale on the heat exchanger surface, which is favorable for heat exchanger fouling.
Funder
National Natural Science Foundation of China
The Ph. D. Programs Foundation of Inner Mongolia University of Technology
Subject
Water Science and Technology,Environmental Engineering
Cited by
8 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献