Affiliation:
1. IEA and Danfoss Analytical, Ellegaardsvej 36, 6400 Soenderborg, Denmark
2. IEA, Lund University, Box 118, SE-221 00 Lund, Sweden
Abstract
In-situ nutrient sensors are now a proven technology. Having ion membranes eliminates the need for ultrafiltration, and consequently the sensors can be located at suitable places in any of the reactors. This gives the potential for new control structures for the control of nitrification, denitrification, and phosphorus removal. In the paper some examples of such controllers are demonstrated as used in a full-scale wastewater treatment plant. A successful control implementation scheme at full-scale plants includes three steps: monitoring, experimenting and controlling. The benefit of implementing process control based on nutrient sensors is real: by implementing precipitation dosage control a savings of 41% compared to flow proportional dosage can be reached, while the savings compared to constant dosage is 73%. An increase in nitrate recirculation shows significant improvement in the nitrogen removal ability at very low cost. Reliable nutrient sensors are not the only prerequisite for a successful control system. The design of actuators, such as drives, compressors and valves, is often overlooked. Furthermore, the lower level controllers have to work properly before the more advanced controllers can work adequately. A collection of practical experience regarding such issues is given in this paper.
Subject
Water Science and Technology,Environmental Engineering
Cited by
16 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献