Affiliation:
1. Stockholm Water Co., SE-106 36 Stockholm, Sweden
Abstract
In response to new demands for increased removal of nitrogen and phosphorus, the Henriksdal and Bromma treatment plants, with hydraulic loads of 283,000 and 148,000 m3/d, respectively, built filtration steps as a final process step in the plants. The denitrification rates in a full-scale and in a pilot plant filter are calculated to 13.1 and 21.3 g (NO3+NO2)-N/(m3·h), respectively, in the total filter bed after 2.5-24.2 and 16.0-28.0 h of operational time, and 6.4 and 18.7 g (NO3+NO2)-N/(m3·h), respectively, after 1.0 and 0.1-0.9 h of operational time. In composite samples, the denitrification rate in the total filter bed is 10-20 g (NO3+NO2)-N/(m3·h) in the full-scale filter. The average values for k = ΔCODf/ΔCT are 1.6 and around 3 in the total filter bed in steady state and in the beginning of the experiments, respectively, both in the full-scale and in the pilot plant study. The carbon source costs for reducing the concentration of nitrate nitrogen in the Bromma plant from 12 to 8 mg/l in the effluent are 117,400 EUR and 147,400 EUR with methanol and ethanol, respectively, as a carbon source.
Subject
Water Science and Technology,Environmental Engineering
Cited by
4 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献