ABSTRACT
The conventional building drainage system was constructed based on the theory of two-phase flow involving water and air. However, the drainage system contained a more intricate three-phase flow, encompassing water, air, and solids, which was relatively overlooked in research. This study addressed the impact of solids on pressure fluctuations, air flow rates, and hydraulic jump fullness within the drainage system, considering three factors: the mass factor, cross-section factor, and viscosity. The investigation was conducted within a single-stack system using both experimental methods and CFD simulations. The findings revealed a positive correlation between both positive and negative pressures and above three factors. The mass factor and the cross-section factor had a more significant impact on the negative pressure of the system. The maximum growth rates of negative pressure extremes under different mass and cross-section factors reached 7.72 and 16.52%, respectively. In contrast, the viscosity of fecal sludge had a slightly higher effect on the positive pressure fluctuation of the drainage system, with the maximum growth rate of positive pressure extremes at 3.41%.