Author:
Chaouche Moustafa Sahnoune,Moulahoum Samir,Houassine Hamza
Abstract
Abstract
The behavior analysis of the transformer is usually achieved by the frequency response analysis (FRA), which is obtained by the application of a very low AC voltage in over a wide frequency range. This paper presents a low and high frequency modelling approach of a three-phase transformer. The developed model consists of a cascade of parallel RLC cells, whose parameters are identified using the frequency response analysis data measurements obtained on each transformer phase. Thus, the proposed model can simulate the frequency behavior of the transformer windings without reference to the geometries of the coils which makes it easily usable in the failure diagnosis field. Experimental results on a 300 VA laboratory transformer validate the proposed model.
Subject
General Physics and Astronomy
Reference44 articles.
1. Evaluación de la Respuesta en Frecuencia del Transformador utilizando un modelo Circuital de Celdas;Revista Energía y Computación,2010
2. Improved Modeling of Power Transformer Winding Using PSO;International Journal of Engineering and Innovative Technology,2013
3. Locating faults in a transformer winding: An experimental study;Electric Power System Research,2009
Cited by
2 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献