Author:
Majchrzak Henryk,Cichoń Andrzej,Borucki Sebastian
Abstract
Abstract
This paper provides an example of the application of the acoustic emission (AE) method for the diagnosis of technical conditions of a three-phase on-load tap-changer (OLTC) GIII type. The measurements were performed for an amount of 10 items of OLTCs, installed in power transformers with a capacity of 250 MVA. The study was conducted in two different OLTC operating conditions during the tapping process: under load and free running conditions. The analysis of the measurement results was made in both time domain and time-frequency domain. The description of the AE signals generated by the OLTC in the time domain was performed using the analysis of waveforms and determined characteristic times. Within the time-frequency domain the measured signals were described by short-time Fourier transform spectrograms.
Subject
Acoustics and Ultrasonics
Reference10 articles.
1. Model - ing of Acoustic Emission Signals Generated in On Load Tap Changer A;Cichoń;Acta Physica Polonica,2014
2. On - line partial discharge calibration and moni - toring for power transformers;Farag;Electric Power Systems Research,1999
3. Acousto - optical PD detection for transformers on Power Delivery;Wang;IEEE Transactions,2006
4. A novel wavelet transform technique for on - line partial discharge measurements : Part On - site noise rejection application on Dielectrics and Electrical;Zhang;IEEE Transactions Insulation,2007
5. Condition Assessment of Power OLTC by Vibration Analysis Using Wavelet Transform on Power Delivery;Rivas;IEEE Transactions,2009
Cited by
23 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献