Affiliation:
1. Department of Electrical Engineering, Bandar Deylam Branch , Islamic Azad University , Bandar Deylam , Iran
Abstract
Abstract
One of transient phenomena that lead to the false trip of the power transformer differential protection during the energization of a loaded power transformer is the ultra-saturation phenomenon. This paper presents, at first, a new algorithm for three-phase power transformer differential protection considering effect of the ultra-saturation phenomenon based on Discrete Wavelet Transform (DWT). To model the ultra-saturation phenomenon, the nonlinear characteristic of the transformer core and the effect of the saturation of the current transformers are taken into account. It is assumed that the load of the transformer is a resistive and inductive load. In this algorithm, the ultra-saturation phenomenon, the external and internal faults of power transformer and the magnetic inrush current are simulated. To distinguish between these phenomena, appropriate criteria using DWT by the use of standard deviation of coefficients are presented. Also, one of the most important criteria for the digital relays is the time for making a decision. Thus, to determine the time of decision, the experimental results will be presented.
Subject
Energy Engineering and Power Technology
Cited by
3 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献