Simulation and experimental analysis of dynamic thermal rise relaxation characteristics for dry-type distribution transformer

Author:

He Dong-sheng12ORCID,Jia Zhi-dong2,Yue Yong-gang2,Wang Ji-xiang3,Xiong Liu-rang1,Xia Shi4,Fu Jian-bing25,He Fa-wu1

Affiliation:

1. Guangzhou Railway Polytechnic , 511365 , Guangzhou , Guangdong Province , China

2. International Graduate School at Shenzhen, Tsinghua University , Nanshan 518055 , Shenzhen , Guangdong Province , China

3. State Key Laboratory of Power Transmission Equipment Technology, School of Electrical Engineering, Chongqing University , Chongqing , China

4. Shenzhen Tiansu Metrology Testing Co., Ltd , Longgang 523000 , Shenzhen Province , China

5. China Electric Power Equipment and Technology Co, Ltd , Beijing 100052 , China

Abstract

Abstract The temperature distribution characteristics of dry-type distribution transformers reflect their overall performance and quality. Distribution transformer daily load changes dramatically, its temperature fluctuates within a certain range. However, most of the research results on transformer temperature rise focus on the steady-state temperature characteristics of transformers, and lack of research related to dynamic temperature rise characteristics. This paper carries out a multi-physics coupling simulation and experimental verification of the dynamic temperature rise relaxation characteristics. The simulation uses the “electromagnetic-flow-thermal” multi-physics coupling analysis method to simulate the steady-state temperature rise characteristics and dynamic temperature rise relaxation characteristics of windings under different load rates. Then, this paper also explores the correlation between the dynamic temperature rise relaxation characteristics and load rate at the typical positions of high-voltage windings and low-voltage windings. The results show that the temperature rise of the winding shows the law of increasing the saturation index function with the increase of the load application time at any load rate. A quantitative characterization model of dynamic temperature rise relaxation behavior at different positions of transformer windings is constructed. It is found that the steady-state temperature rise value of different parts of the winding increases regularly as a power function with the increase of load rate, while the constant value of dynamic temperature rise relaxation time in different parts of the winding decreases as a power function with the increase of load rate. The verification results of the quantitative characterization model of dynamic temperature rise relaxation behavior show that the maximum error of the measured and theoretical steady-state temperature rise value is only 1.56 K, and the maximum error of the constant value of dynamic temperature rise relaxation time is only 0.082 h. These findings provide valuable insights into the performance and quality of dry-type distribution transformers, and can help improve their design and operation for better efficiency and safety.

Publisher

Walter de Gruyter GmbH

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3