Abstract
On the base of analyses on the development of the construction industry as well as fires occurring in Kazakhstan, the article justifies the areas of fire prevention related to technical regulation that is the certification of materials, construction structures and engineering systems. The translucent building structures have increasing application in modern construction techniques. For such structures, the most vulnerable indicator is the fire resistance limit. A technical solution is offered to increase this indicator by using water irrigation. On the base of existing international and national regulatory documents, a number of methods has been developed for experimental determination of the actual fire resistance limit by cooling of structures with water in case of fire. Large-scaled fire researches have been carried out to determine the actual limit of fire resistance of the translucent partition made of tempered glass "Float" with the thickness of 12 mm, M1 grade both in the presence of water irrigation and in the absence thereof. The tests were carried out under standard and actual fire conditions. Optimal parameters of water irrigation are determined. On the base of research results, it is proposed to improve the construction standards in this field as well as methodological documents in the field of certification tests.
Publisher
National Academy of Sciences of the Republic of Kazakshtan
Subject
Geology,Geotechnical Engineering and Engineering Geology