Electricity consumption characteristics and prediction model of a large airport terminal in Beijing

Author:

Yang Yi,Chen Chao,Li Zhiyong,Guan Dongya,Su Feifei

Abstract

AbstractThe large airport terminal is the city's transportation hub and logistics center, and its building electricity consumption is twice or even higher than that of general large public buildings. Energy-saving and consumption reduction of the terminal building is not only the need to improve the operational efficiency and reduce the operation cost of the airport but also the need to realize the goal of "double carbon" in China. In this study, a large airport terminal in Beijing is taken as the research object. According to the characteristics of its main electrical equipment system, and the measured data of passenger flow from January 2020 to February 2023, combined with Pearson correlation analysis, K-means cluster analysis and multiple regression analysis, the influence and correlation characteristics of building scale, passenger flow and outdoor meteorological parameters on its electricity consumption are analyzed. The results show that: 1) The daily electricity consumption of the terminal can be analyzed by five levels according to the daily passenger flow, namely, 10,000 < N ≤ 30,000,30,000 < N ≤ 50,000, 50,000 < N ≤ 70,000, 70,000 < N ≤ 100,000, and 100,000 < N ≤ 130,000; 2) The electricity consumption of the terminal can be divided into three categories: basic electricity consumption related to the building scale of the terminal, variable electricity consumption I related to passenger flow, and variable electricity consumption II related to outdoor air temperature and passenger flow. Based on this, the terminal's daily electricity consumption prediction model is constructed, and the measured data verify the model's effectiveness. 3) Put forward the evaluation reference value of the daily electricity consumption of different passenger flow in this terminal, When the year passenger flow reaches the design value of 45 million, the normal daily electricity consumption level ranges from 0.44 to 0.48 kW·h/(m2·day). The research results can provide methods and evaluation reference for electricity consumption prediction, and accurate control of electricity consumption of main equipment systems in airport terminal.

Funder

Key Projects of Civil Aviation Joint Fund of National Natural Science Foundation of China.

Publisher

Springer Science and Business Media LLC

Reference31 articles.

1. Airport Department of Civil Aviation Administration of China (2017) Investigation and Test Report on Green Performance of Civil Airport Terminal: IB-CA-2017–01. Civil Aviation Administration of China, Beijing

2. Balaras CA (2003) Energy conservation potential, HVAC installations and operational issues in Hellenic airports. Energy Build 35(11):1105–1120

3. Cardonae E, Piacentinoa A, Cardonaf F (2006) Energy saving in airports by trigeneration. Part I: assessing economic and technical potential. Appl Therm Eng 26(14):1427–1436

4. China Building Energy Conservation Association.China Building Energy Conservation Report (2016) Construction. energy consumption statistics committee of china building energy conservation association. 2020 China building energy consumption report. Archit 2019(2):6–31

5. Civil Aviation Administration of China (2017) Guidelines for Energy Efficiency Evaluation of Civil Airport Terminals: MT/MT/T5112-2016. China Civil Aviation Press, Beijing