Small signal stability analysis of a four-machine system with placement of multi-terminal high voltage direct current link

Author:

Oni Oluwafemi E.ORCID,Swanson Andrew G.ORCID,Carpanen Rudiren PillayORCID

Abstract

Inter-area oscillation caused by weak interconnected lines or low generator inertia is a critical problem facing power systems. This study investigated the performance analysis of a multi-terminal high voltage direct current (MTDC) on the damping of inter-area oscillations of a modified two-area four-machine network. Two case studies were considered, utilising scenario 1: a double alternating current (AC) circuit in linking Bus_10 and Bus_11; and scenario 2: a three-terminal line commutated converter high voltage direct current system in linking Bus_6 and Bus_11 into Bus_9. It was found that scenario 2 utilising MTDC link with a robust controller provided quick support in minimising the network oscillations following a fault on the system. The MTDC converter controllers’ setup offered sufficient support for the inertia of the AC system, thus providing efficient damping of the inter-area oscillation of the system.

Publisher

Academy of Science of South Africa

Subject

General Energy,General Computer Science

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估