Experimental Description of Information Technology Equipment Reliability Exposed to a Data Center Using Airside Economizer Operating in Recommended and Allowable ASHRAE Envelopes in an ANSI/ISA Classified G2 Environment

Author:

Awe Oluwaseun1,Shah Jimil M.1,Agonafer Dereje1,Singh Prabjit2,Kannan Naveen3,Kaler Mike3

Affiliation:

1. Mechanical and Aerospace Engineering Department, University of Texas at Arlington, Arlington, TX 76019

2. IBM Corporation, 2455 South Road, Poughkeepsie, NY 12601

3. Mestex, a Division of Mestek, Inc., 4830 Transport Drive, Dallas, TX 75247

Abstract

Abstract Airside economizers lower the operating cost of data centers by reducing or eliminating mechanical cooling. It, however, increases the risk of reliability degradation of information technology (IT) equipment due to contaminants. IT Equipment manufacturers have tested equipment performance and guarantee the reliability of their equipment in environments within ISA 71.04-2013 severity level G1 and the ASHRAE recommended temperature-relative humidity (RH) envelope. IT Equipment manufacturers require data center operators to meet all the specified conditions consistently before fulfilling warranty on equipment failure. To determine the reliability of electronic hardware in higher severity conditions, field data obtained from real data centers are required. In this study, a corrosion classification coupon experiment as per ISA 71.04-2013 was performed to determine the severity level of a research data center (RDC) located in an industrial area of hot and humid Dallas. The temperature-RH excursions were analyzed based on time series and weather data bin analysis using trend data for the duration of operation. After some period, a failure was recorded on two power distribution units (PDUs) located in the hot aisle. The damaged hardware and other hardware were evaluated, and cumulative corrosion damage study was carried out. The hypothetical estimation of the end of life of components is provided to determine free air-cooling hours for the site. There was no failure of even a single server operated with fresh air-cooling shows that using evaporative/free air cooling is not detrimental to IT equipment reliability. This study, however, must be repeated in other geographical locations to determine if the contamination effect is location dependent.

Publisher

ASME International

Subject

Electrical and Electronic Engineering,Computer Science Applications,Mechanics of Materials,Electronic, Optical and Magnetic Materials

Reference23 articles.

1. ASHRAE DOE Course: Save Energy Now Presentation Series;ASHRAE Technical Committee 9.9,2010

2. Shah, J. M., 2016, “ Reliability Challenges in Airside Economization and Oil Immersion Cooling,” Master's thesis, University of Texas at Arlington, Arlington, TX.https://www.researchgate.net/publication/315726572_Reliability_challenges_in_airside_economization_and_oil_immersion_cooling

3. Effect of Relative Humidity, Temperature and Gaseous and Particulate Contaminations on Information Technology Equipment Reliability,2015

4. Thermal Guidelines for Data Processing Environments (ASHRAE Datacom Series);ASHRAE Technical Committee 9.9,2004

5. Thermal Guidelines for Data Processing Environments (ASHRAE Datacom Series);ASHRAE Technical Committee 9.9,2008