Pumpless Loop for Narrow Channel and Micro-Channel Boiling
Author:
Mukherjee Swaraj1, Mudawar Issam1
Affiliation:
1. Purdue University International Electronic Cooling Alliance (PUIECA), West Lafayette, IN 47907
Abstract
A compact cooling system is examined which capitalizes upon fluid density differences between two vertical, parallel, interconnected tubes to achieve a pumpless cooling loop. A heat-dissipating device is incorporated into a boiler at the bottom of the hot tube. The large density differences between the two tubes produces a substantial nonequilibrium in hydrostatic pressure, drawing liquid downwards through the cold tube as a two-phase mixture is released upwards in the hot tube. Cooling with this pumpless loop is fundamentally different from, and far superior to, pool boiling thermosyphons because of the former’s ability to separate the path of replenishment liquid from that of the released vapor. Experiments were performed to explore the effects of boiler gap (separation distance between the boiling surface and opposite insulating wall) on cooling performance and critical heat flux (CHF) for water and FC-72. The gap, which is the primary measure of boiler miniaturization, was varied from 0.051 to 21.46 mm. For large gaps, CHF showed insignificant dependence on the gap for both fluids. However, small gaps produced CHF variations that were both drastic and which followed opposite trends for the two fluids. Decreasing the gap below 3.56 mm produced a substantial rise in CHF for FC-72. For water, CHF was fairly insensitive down to 0.51 mm, below which it began to decrease sharply. These trends are shown to be closely related to the small surface tension and contact angle of FC-72 producing very small bubbles which can easily pass through narrow gaps in FC-72, while much larger bubbles in water obstruct liquid replenishment in narrow gaps. A numerical model is constructed to determine how the gap influences the various components of pressure drop, velocities, coolant flow rate, and hence system response to heat input.
Publisher
ASME International
Subject
Electrical and Electronic Engineering,Computer Science Applications,Mechanics of Materials,Electronic, Optical and Magnetic Materials
Reference14 articles.
1. Mudawar, I.
, 2001, “Assessment of High-Heat-Flux Thermal Management Schemes,” IEEE Trans. Compon., Packag. Manuf. Technol., Part A, 24, pp. 122–141. 2. Boyd, R. D.
, 1985, “Subcooled Flow Boiling Critical Heat Flux (CHF) and its Application to Fusion Energy Components—Part I. A Review of Fundamentals of CHF and Related Data Base,” Fusion Technol., 7, pp. 7–31. 3. Mudawar, I., and Bowers, M. B., 1999, “Ultra-High Critical Heat Flux (CHF) for Subcooled Water Flow Boiling—I. CHF Data and Parametric Effects for Small Diameter Tubes,” Int. J. Heat Mass Transfer, 42, pp. 1405–1428. 4. Rogers, C. S., Mills, D. M., Lee, W. K., Knapp, G. S., Holmberg, J., Freund, A., Wulff, M., Rossat, M., Hanfland, M., and Yamaoka, H., 1995, “Performance of a Liquid-Nitrogen-Cooled, Thin Silicon Crystal Monochromator on a High-Power, Focussed Wiggler Synchrotron Beam,” Rev. Sci. Instrum., 66, pp. 3494–3499. 5. Tuckerman, D. B., and Pease, R. F. W., 1981, “High-Performance Heat Sinking for VLSI,” IEEE Electron Device Lett., EDL-2, pp. 126–129.
Cited by
82 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献
|
|