Affiliation:
1. Laboratory for Refrigeration and District Energy, Faculty of Mechanical Engineering, University of Ljubljana, Ljubljana 1000, Slovenia e-mail:
Abstract
This paper presents the results of a thermo-economic (TE), primary-energy-factor and CO2-equivalent (CO2 (eq)), emissions-sensitivity analysis for the preparation of sanitary hot water (SHW) in fourth-generation district-heating systems. The annual required additional heat for the SHW provided by a local heating unit, based on an air-to-water heat pump (AWHP), a natural-gas boiler (NG boiler), and an electrical resistance heater (ERH), was determined using a trnsys simulation. Additionally, the seasonal performance factor (SPF) of the HP under consideration was determined. The study considered three possible supply temperatures, i.e., 35, 40, and 45 °C. The results show that a local heating unit based on an AWHP is most efficient in terms of the used primary energy (PE) and CO2 (eq) emissions. This unit is also the second best in terms of TE performance. The unit based on a NG boiler is much more appropriate than an ERH unit in terms of both the primary energy factor (PEF) and the CO2 (eq) emission factors for an electricity generation mix (EGM) that has values higher than the average for the EU-28. The heat generated by this NG unit is also cheaper than the heat produced by an ERH based on the average price for electricity in the EU-28.
Subject
Geochemistry and Petrology,Mechanical Engineering,Energy Engineering and Power Technology,Fuel Technology,Renewable Energy, Sustainability and the Environment