Affiliation:
1. Department of Building Services Engineering, The Hong Kong Polytechnic University, Hung Hom, Hong Kong, China
Abstract
This paper describes how direct evaporative coolers can be used to improve the energy efficiency of air-cooled chillers in various operating conditions and with different strategies for staging condenser fans. These coolers are installed in front of air-cooled condensers to precool outdoor air before entering the condensers. A simulation analysis on an air-cooled chiller equipped with a direct evaporative cooler showed that when head pressure control is used, the cooler enables the condensing temperature to drop by 2.1–6.2°C, resulting in a 1.4-14.4% decrease in chiller power and a 1.3–4.6% increase in the refrigeration effect. When the chiller with the cooler operates under condensing temperature control, where condenser effectiveness is enhanced by staging all condenser fans, there is a savings in chiller power of 1.3-4.3% in some operating conditions in which the drop in compressor power exceeds the additional condenser fan power due to the pressure drop across the cooler.
Subject
Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment
Cited by
24 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献