Abstract

Experiments are carried out here to measure the evaporation heat transfer coefficient hr and associated frictional pressure drop ΔPf in a vertical plate heat exchanger for refrigerant R-410A. The heat exchanger consists of two vertical counterflow channels which are formed by three plates whose surface corrugations have a sine shape and a chevron angle of 60 deg. Upflow boiling of refrigerant R-410A receives heat from the hot downflow of water. In the experiments, the mean vapor quality in the refrigerant channel is varied from 0.10 to 0.80, the mass flux from 50 to 100 kg/m2s, and the imposed heat flux from 10 to 20 kW/m2 for the system pressure fixed at 1.08 and 1.25 MPa. The measured data indicate that both hr and ΔPr increase with the refrigerant mass flux except at low vapor quality. In addition, raising the imposed heat flux is found to significantly improve hr for the entire range of the mean vapor quality. However, the corresponding friction factor ftp is insensitive to the imposed heat flux and refrigerant pressure. Based on the present data, empirical correlations are provided for hr and ftp, for R-410A in the plate heat exchanger.

Publisher

ASME International

Subject

Mechanical Engineering,Mechanics of Materials,Condensed Matter Physics,General Materials Science

Cited by 77 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3