Affiliation:
1. Heat Transfer and Thermal Power Laboratory, Department of Mechanical Engineering, Indian Institute of Technology Madras, Chennai-600 036 (INDIA)
Abstract
A detailed experimental study on flow maldistribution from port to channel of a plate heat exchanger is presented. In general, flow maldistribution brings about an increase in pressure drop across the heat exchanger. This increase is found to depend on flow rate, number of channels and port size. Experiments show that analytical predictions of pressure drop including maldistribution effect are quite accurate for practical purposes. The results indicate that under identical conditions, maldistribution is more severe in Z-type plate heat exchanger compared to U type. Experiments are also carried out under non-isothermal realistic operating conditions, which show increased flow maldistribution at elevated temperature. Finally predictions are made for industrial plate heat exchangers, which show the limitation of adding additional plates beyond a certain limit. An insight to the physical aspects of maldistribution and its possible reduction through proper design strategy is also indicated.
Cited by
66 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献