Affiliation:
1. School of Mechanical System Engineering, Incheon National University, Songdo-Dong, Yeonsu-gu Incheon, 406-772, Republic of Korea
Abstract
In the present study, pool boiling heat transfer coefficients in Lithium Bromide ( LiBr ) solution were obtained for smooth, floral, notched fin and notched floral tubes. Test range covered saturation pressure from 7.38 to 101.3 kPa, LiBr concentration from 0% to 50%. Floral tube yielded the highest heat transfer coefficient, and smooth tube yielded the lowest heat transfer coefficient. Effect of notching on heat transfer coefficient was dependent on tube shape. When applied to the smooth tube (notched fin tube), notching increased the heat transfer coefficient. When applied to the floral tube (notched floral tube), on the other hand, notching decreased the heat transfer coefficient. The reason has been attributed to the balance of advantage of added nucleation sites and disadvantage of added flow resistance. Boiling heat transfer correlations were developed which are applicable for saturation pressure from 7.38 to 101.3 kPa and LiBr concentration from 0% to 50%.
Publisher
Springer Science and Business Media LLC
Subject
Fluid Flow and Transfer Processes,Renewable Energy, Sustainability and the Environment,Control and Systems Engineering
Cited by
8 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献