Abstract
Cooling circuits can be improved by using a desuperheater. A series connected desuperheater increases the efficiency of the circuit and allows the waste heat to be used, e.g., for DHW preparation. The study investigates the behavior of a parallel connected desuperheater for DHW preparation in an experimental cooling circuit. The basic parameters of the cooling circuit (efficiency, pressure, temperature and energy consumption) were evaluated when operating 1. with only a condenser and 2. with a condenser and a desuperheater connected in parallel. The results of the study show that a parallel connected condenser and desuperheater reduces the overall efficiency of the cooling circuit.
Publisher
Periodica Polytechnica Budapest University of Technology and Economics
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献