Affiliation:
1. ELTRA, Fjordvejen 1-11, DK-7000 Fredericia, Denmark
Abstract
One of the main concerns of grid-integration of large wind farms with variable-speed wind turbines equipped with doubly-fed induction generators controlled by back-to-back converters is a possible risk of mutual interaction between the control systems of the converters. This topic is discussed and illustrated by simulations on a large wind farm model consisting of eighty wind turbines, when subjected to a short-circuit fault. At no mutual interaction, the wind turbines show coherent response at the grid fault. In such a case, large wind farms can be represented by one-machine equivalent, e.g. one wind turbine model with re-scaled power capacity. This simplification can be applied for voltage stability investigations carried out on detailed models of large power systems.
Subject
Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment
Cited by
22 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献