Author:
Jo Jae Geun,Lee Chi Young
Abstract
In this study, numerical simulations to investigate the effects of the spray characteristics of water mist on thermal radiation attenuation were performed using fire dynamics simulator (FDS). The droplet size, flow rate, and spray angle of the water mist were 100-300 µm, 1-3 L/min, and 60-180°, respectively. As the droplet size decreased and flow rate increased, the thermal radiation attenuation increased. When the spray angles decreased and increased behind the near nozzle center and behind a certain remote distance from the nozzle center, respectively, the thermal radiation attenuation increased. The peak thermal radiation attenuation increased with decreases in droplet size and spray angle and an increase in flow rate, whereas the average thermal radiation attenuation increased with a decrease in droplet size and increases in flow rate and spray angle. Under the numerical simulation conditions of this study, the peak and average thermal radiation attenuations were significantly altered by the ratios of droplet size and flow rate and by that of flow rate, respectively. However, their variations with the ratio of spray angle were the smallest.
Funder
Ministry of Science and ICT
National Research Foundation of Korea
Publisher
Korea Institute of Fire Science and Engineering
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献