Abstract
This paper presents an adsorption cooler (AC) driven by the surplus heat of a solar thermal domestic hot water system to provide cooling to residential buildings. A cylindrical tube adsorber using granular silica gel as adsorbent and water as adsorbate was considered. The AC was modelled using a two-dimensional distributed parameter model implemented in previous adsorption heating and cooling studies. The performance coefficients of the resultant thermally driven cooling system were obtained for a broad range of working conditions. The thermally driven AC was found to have coefficient of performance (COP) of 0.5 and a specific cooling power (SCP) of 44 W·kg−1 when considering condenser, evaporator, and regeneration temperatures of 30 °C, 15 °C, and 70 °C, respectively. Moreover, the results showed that the AC could be used for refrigeration purposes at temperatures as low as 2 °C and that it could also operate during hotter days under temperatures of 42 °C.
Funder
Fundação para a Ciência e a Tecnologia
European Regional Development Fund
Subject
General Earth and Planetary Sciences,General Environmental Science
Cited by
3 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献