Author:
Luo Derong,Wu Ting,Li Ming,Yi Benshun,Zuo Haibo
Abstract
Accurate detection of ripple components of the direct-current (DC) signals is essential for evaluating DC power quality. In this study, the combination algorithm based on variational mode decomposition (VMD) and Hilbert transform (HT) is applied to detect and analyze the characteristics of the ripple components of the DC disturbance signals. Firstly, the optimal modal number of VMD algorithms is comprehensively determined by observing the center frequencies of the mode components and the Index of Orthogonality (IO) of mode components. Through utilizing the VMD algorithm, the DC disturbance signal is accurately decomposed into a series of amplitude modulation-frequency modulation (AM-FM) functions. Then, the HT algorithm is applied to each AM-FM function to obtain the corresponding instantaneous amplitude and frequency, and the characteristics of DC disturbance signal are determined. Some case studies are implemented to analyze the ripple components of the DC disturbance signal with the VMD-HT and empirical mode decomposition (EMD) algorithm. Finally, the experiment results of Gree Photovoltaic Cabin have verified the feasibility and effectiveness of the proposed combination VMD-HT algorithm by comparison with EMD and the window interpolation fast Fourier transform (WIFFT) algorithms.
Funder
the National Key Research and Development Program of China
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
9 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献