Quantifying Energy Savings from Optimal Selection of HVAC Temperature Setpoints and Setbacks across Diverse Occupancy Rates and Patterns

Author:

Talami Riccardo1,Dawoodjee Ilyas1,Ghahramani Ali1ORCID

Affiliation:

1. Department of the Built Environment, National University of Singapore, Singapore 117566, Singapore

Abstract

With the advent of flexible working arrangements, we are observing a dramatic shift in how buildings are occupied today, which presents an opportunity to optimize Heating, Ventilation, and Air Conditioning system temperature setpoints based on variations in occupancy. Guidelines often suggest the adoption of the highest or lowest setpoint or setback to minimize energy consumption in hot or cold climates, respectively. However, at outdoor temperatures where variations in occupancy heat loads prompt buildings to fluctuate across cooling, free-running, and heating mode, optimal setpoints and setbacks are not always the lowest or highest. In addition, the perturbations caused by rapid switching between setpoint and setback could diminish energy savings due to system destabilization. This paper aims to systematically compare the potential energy savings from fixed and optimal setpoints and setbacks across wide-ranging occupancy scenarios (four occupancy rates and 14 patterns). Energy simulations were conducted using the Department of Energy reference models for small, medium, and large office buildings to enable an exhaustive search of optimal setpoint/setbacks in 17 climate zones. Explored setpoints were 19.5 °C to 25.5 °C with intervals of 1 °C, and setbacks were 17 °C/19 °C for heating and 26 °C/28 °C for cooling. The findings indicate that, on average, while lower occupancy heat loads results in 5.48% energy reduction, a conventional fixed setpoint and setback strategy provides an additional 11.80%, and optimal selection of setpoints and setbacks could provide an additional 34.36–38.08%, emphasizing the untapped potential energy saving. To facilitate practical applications, this paper presents an interactive graphical interface: Optimal Temperature Setpoint Tool.

Funder

Singapore Ministry of Education

Publisher

MDPI AG

Subject

Building and Construction,Civil and Structural Engineering,Architecture

Reference38 articles.

1. A review on buildings energy consumption information;Ortiz;Energy Build.,2008

2. ASHRAE (2017). ASHRAE Handbook—Fundamentals, American Society of Heating, Refrigerating and Air-Conditioning Engineers.

3. Early-design sensitivity of radiant cooled office buildings in the tropics for building performance;Talami;Energy Build.,2020

4. Talami, R., and Jakubiec, J.A. (2019, January 2–4). Sensitivity of Design Parameters on Energy, System and Comfort Performances for Radiant Cooled Office Buildings in the Tropics. Proceedings of the 16th IBPSA International Conference, Rome, Italy.

5. (2015). Ergonomics of the Thermal Environment—Analytical Determination and Interpretation of Thermal Comfort Using Calculation of the PMV and PPD Indices and Local Thermal Comfort CriteriaEN ISO 7730.