Abstract
The Gas-insulated Line (GIL) is a technical equipment that allows power transmission underground at high voltage level. The UHV GIL-overhead hybrid transmission line is an essential way for power transmission in complicated landscapes. Because of the distributed capacitance of the UHV transmission line and the difference of the structure and the electrical parameters between GIL and overhead transmission line, the distance protection based on uniform lumped parameters cannot be applied to this hybrid transmission line directly. In order to overcome the shortcomings, this paper studies and proposes a new principle of distance protection for the UHV GIL-overhead hybrid transmission line based on frequency domain lossless transmission line equation, with the distributed capacitance accounted. Then, the paper presents a setting scheme for this distance protection with the hybrid line parameters considered. Finally, tests are carried out on the Power Systems Computer Aided Design (PSCAD) platform, and the accuracy and reliability of the distance protection method proposed are verified by simulation results.
Funder
Innovative Research Group Project of the National Natural Science Foundation of China
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献