Abstract
Grid-connected voltage source converters (GC-VSCs) are used for interfacing the distributed power generation system (DPGS) to the utility grid. Performance of the current loop is a critical issue for these GC-VSCs. Recently, reduced order generalized integrator (ROGI)-based current controller is proposed, such that AC reference signal of positive or negative sequences can be separately tracked without steady-state error, which has the advantage of less computational burden. However, the cross-coupling within the ROGI-based current controller would deteriorate the transient response of the current loop. In this paper, a ROGI-based decoupled current controller is proposed to eliminate the coupling between α -axis and β -axis. Thus, the faster dynamic response performance can be achieved while maintaining the merits of ROGI-based current controller. An optimal gain parameter design method for the proposed current controller is presented to improve the stability and dynamic response speed of current loop. Simulation and experiments were performed in MATLAB/Simulink and TMS320C28346 DSP-based laboratory prototype respectively, which validated the proposed theoretical approach.
Funder
National Natural Science Foundation of China
China Postdoctoral Science Foundation
Fundamental Research Funds for the Central Universities
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
7 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献