Frequency of Damage of Low Voltage Apparatus Due to Lightning Flashes to Ground Nearby HV Overhead Lines

Author:

Kisielewicz Tomasz,Piparo Giovanni Battista Lo,Mazzetti Carlo

Abstract

The paper deals with a simplified approach to evaluate the frequency of damage of low voltage apparatus powered by a in housing HV/LV transformer against overvoltages due to nearby lightning flashes (source of damage S4 according to IEC 62,305 standard). The approach is based on computer simulations with validated models according to the current state of the art. The paper evaluates: the overvoltages stressing the HV/LV transformer due to lightning-induced over-voltages on the supplying HV overhead line; the voltage transferred to low voltage circuit through the power transformer and the influence of the transformer characteristics and of the LV circuits feeding the apparatus; the influence of the characteristics and the number of LV circuits on the frequency of damage of the apparatus. The different contributions to the voltage at the apparatus terminals, namely, the voltage transferred by the HV/LV transformer and the voltage induced by lightning current in the circuit downstream the transformer, are recognized. The voltage drop along the earthing system between the points where the transformer and the apparatus are earthed is, in the case considered, not effective because the apparatus and the transformer are bonded at the same point to the earthing system of the electrical installation. Even if these voltage components exhibit different shape and time at peak, for safety, they are added. When the resulting voltage is higher than the rated impulse voltage of apparatus insulation, damage of apparatus occurs. The evaluation allows to conclude that the frequency of damage of the LV apparatus supplied by circuits in a multipolar cable is about a thousand times lower than the one relevant to circuits in plastic conduit. If the tolerable frequency of damage of the LV apparatus is kept in the range of 0.01 damage/year, the adoption of protection measures against overvoltages caused by the source S4 is practically not necessary, except for the case of long circuits in conduit, powered by long HV overhead lines in areas with high values of lightning flash density. As this matter has not yet been considered in the IEC 62305 standard series, the results presented in this paper will be useful in the light of the revision of requirements of this standard.

Funder

Warsaw University of Technology, Poland

Rome “La Sapienza”, Italy

Publisher

MDPI AG

Subject

Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous),Building and Construction

Reference43 articles.

1. Quality of the supplied electric service: A tool to evaluate the need of protection against lightning surges

2. SPD dimensioning in front of indirect flashes to overhead low voltage power lines;Kisielewicz;Proceedings of the 15 IEEE International Conference on Environment and Electrical Engineering,2015

3. Simplified approach for protection of apparatus powered by an HV/LV transformer against lightning strokes to the structure;Kisielewicz;Proceedings of the 22 IEEE International Conference on Environment and Electrical Engineering,2022

Cited by 2 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3