Analysis of Fine Fault Electrothermal Characteristics of Converter Transformer Reduced-Scale Model

Author:

Zhou Xiu1,Luo Yan1ORCID,Zhu Lin2,Bai Jin1,Tian Tian1,Liu Bo3,Xu Yuhua1,Zhao Wenliang4

Affiliation:

1. Electric Power Research Institute of State Grid Ningxia Electric Power Co., Ltd., Yinchuan 750002, China

2. State Grid Ningxia Electric Power Co., Ltd, Yinchuan 750001, China

3. Ultra-High Voltage Company of State Grid Ningxia Electric Power Co., Ltd., Yinchuan 750011, China

4. School of Electrical Engineering, Shandong University, Jinan 250100, China

Abstract

Converter transformer is the key equipment in UHVDC transmission. If a local overheating fault occurs, it will inevitably form a local hot spot on the core, winding or other structural parts. Among these faults, multipoint grounding and interlaminar short circuit faults account for 30–50% of core accidents. The continuous overheating of 150–250 °C will cause ablation on the silicon steel sheet, which will destroy the insulation material and reduce the insulation performance. In severe cases, it will cause thermal expansion, resulting in local deformation or displacement of the core. Considering the scale of size and temperature parameters, the scale model of converter transformer is established based on the principle of constant magnetic flux density. By using the homogenization theory, the scaled model under multipoint grounding and interlaminar short circuit fault is simulated by electromagnetic heat. First, the single-phase four-column model of the core is established according to the scaled principle, and the core is refined. Secondly, taking the refined model as the research object, the magnetic thermal coupling simulation and analysis are carried out under multi-point grounding and interlaminar short circuit fault, and the magnetic density, eddy current loss and temperature distribution on each lamination are obtained. Finally, the correctness of the simulation is verified by the one-dimensional eddy current loss analytical equation, which provides a reference for the local overheating problem of converter transformers.

Funder

State Grid Ningxia Electric Power Co., LTD.

Publisher

MDPI AG

Reference31 articles.

1. Dragan, J. (2019). High Voltage Direct Current Transmission, John Wiley & Sons, Ltd.

2. Dynamic Risk Assessment Framework for Industrial Systems Based on Accidents Chain Theory: The Case Study of Fire and Explosion Risk of UHV Converter Transformer;Feng;Reliab. Eng. Syst. Saf.,2022

3. Research on Distribution Characteristics of Vibration Signals of ±500 kV HVDC Converter Transformer Winding Based on Load Test;Jiang;Int. J. Electr. Power Energy Syst.,2021

4. Numerical prediction of losses and local overheating in transformer windings based on magnetic-thermal-fluid model;Li;Trans. China Electrotech. Soc.,2020

5. Experiment on vibro-acoustic characteristic of 500 kV single-phase transformer under DC-bias;Li;Trans. China Electrotech. Soc.,2021

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3