Abstract
This paper proposes an equivalent circuit model to obtain the transient electrical stress quantitatively in medium voltage medium frequency transformers in modern power electronics. To verify this model, transient simulation is performed on a 1.5 kV/1 kHz transformer, revealing voltage overshoot quantitatively between turns and layers of the transformer’s HV winding. Effects of rise time of the input pulse voltage, stray capacitance of the winding insulation, and their interactions on the voltage overshot magnitude are presented. With these results, we propose limiting the voltage overshoot and, thereafter, enhancing medium voltage medium frequency transformer’s insulation capability, which throws light on the transformer’s insulation design. Additionally, guidance on the future studies on aging and endurance lifetime of the medium voltage medium frequency transformer’s insulation could be given.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
2 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献