A Static and Dynamic Analysis of Photovoltaic Penetration into MV Distribution Network

Author:

Maghami Mohammad Reza1ORCID,Pasupuleti Jagadeesh2ORCID,Ling Chee Mei3

Affiliation:

1. Uniten R&D Sdn. Bhd, Universiti Tenaga Nasional, Jalan Ikram-Uniten, Kajang 43000, Selangor, Malaysia

2. Institute of Sustainable Energy, Universiti Tenaga Nasional, Jalan Ikram-Uniten, Kajang 43000, Selangor, Malaysia

3. Centre for Research in Data Science, Universiti Teknologi Petronas, Seri Iskandar 32610, Perak Darul Ridzuan, Malaysia

Abstract

Photovoltaic (PV) systems are becoming increasingly prevalent worldwide, particularly in power distribution networks. However, their intermittency and integration into distribution networks can have adverse effects. This study investigates the impact of large-scale solar integration into a typical Malaysian power grid network, focusing on voltage stability, short circuits, and power loss under peak and no-load conditions. Using Digsilent Power Factory software, static and dynamic power flow analyses were performed on a network consisting of two 132/11 kV transformers, an 11 kV busbar, and 112 loads served through eight feeders. Solar PV of 100 kW was integrated into each node, and the maximum allowable solar grid connection level was determined. The static results show that there were no violations in no-load conditions at 100 kW PV penetration. However, during peak load, there were violations at 0% PV penetration, but by increasing the level of solar grid connection to 60% (60 kW), the voltage level moves up to the acceptable range. Under contingency conditions, the results show that the minimum level of solar penetration is 80% (80 kW). The highest power loss occurs during peak time and is observed at 0% PV penetration. Feeder 8, the lounge feeder with the highest number of loads, is identified as the main cause of power loss. According to the short circuit analysis in peak and no-load conditions, the system experiences the highest shorts during peak loads. On the other hand, we conducted a dynamic simulation with load characteristics and compared the results for different levels of PV penetration. The results from the dynamic simulations show that lower limit violations occur even at 100% PV penetration for a brief period in all case studies. This study identifies the maximum permissible PV penetration as 125 kW.

Funder

BOLDREFRESH2025-CENTRE OF EXCELLENCE

Publisher

MDPI AG

Subject

Process Chemistry and Technology,Chemical Engineering (miscellaneous),Bioengineering

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3