Comparison of Portable and Large Mobile Air Cleaners for Use in Classrooms and the Effect of Increasing Filter Loading on Particle Number Concentration Reduction Efficiency

Author:

Duill Finn Felix1ORCID,Schulz Florian1,Jain Aman2ORCID,van Wachem Berend2ORCID,Beyrau Frank1

Affiliation:

1. Institute of Fluid Dynamics and Thermodynamics, Otto von Guericke University Magdeburg, 39106 Magdeburg, Germany

2. Institute of Process Engineering, Otto von Guericke University Magdeburg, 39106 Magdeburg, Germany

Abstract

This study focuses on the effect of portable and large filter-based air cleaners (HEPA filters), which became popular indoors during the COVID-19 pandemic, and their suitability for classrooms (here 186 m3). The decay rates of the particle number concentration (PNC) were measured simultaneously at up to four positions in the room. It was found that the different air outlet configurations of the units have an effect on the actual PNC removal in the room when operated at the same volume flow rates. This effect of the airflow efficiency of the air cleaners (AP) in a classroom is quantified with an introduced Air Cleaning Efficiency Factor in this study to identify beneficial airflows. In this context, the effect of filter loading in long-term operation on the cleaning effect is also investigated. The emitted sound pressure levels of the APs are given special attention as this is a critical factor for use in schools, as well as power consumption. A total of six different devices were tested—two portable APs and four large APs. In order to achieve the necessary volume flow rates, three or four of the portable units were used simultaneously in one room, while only one of the large units was used per room. When used at the same air circulation rates in the room, the portable APs exhibit higher sound pressure levels compared to the large APs. At air circulation rates of 4–5 h−1, the portable APs exceeded a value of 45 dB(A). Two of the four large units reach sound pressure levels below 40 dB(A) at air circulation rates of 4–5 h−1, whereby both large units, which are positioned on the rear wall, realize a homogeneous dilution of the room air. This is achieved by an air outlet directed horizontally at a height above 2 m or diagonally towards the ceiling, which points into the room and partly to the sides. On the other hand, an air outlet directed exclusively to the sides or horizontally into the room at floor level to all sides achieves lower particle decay rates. To investigate the influence of the filter loading, three large APs were operated in a school for a period of one year (190 days with 8 h each). For the three APs, long-term operation leads to different changes in PNC reduction efficiency, ranging from −3% to −34%. It is found that not only the size of the prefilter and main filter has a significant influence, but also whether there is a prefilter bypass that negatively affects the loading level of the main filter. At the same time, it was shown that one type of AP, measuring the pressure drop across the filters and readjusting the fan, kept the circulation rate almost constant (up to −3%) over a year.

Funder

Ministry of Economy, Science, and Digitalization

Publisher

MDPI AG

Subject

Atmospheric Science,Environmental Science (miscellaneous)

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3