Demand Side Management Effects on Substation Transformer Capacity Limits

Author:

McBee Kerry D.,Chong Jacquelyn,Rudraraju Prasanth

Abstract

In high penetrations, demand side management (DMS) applications augment a substation power transformer’s load profile, which can ultimately affect the unit’s capacity limits. Energy storage (ES) applications reduce the evening peaking demand, while time-of-use rates incentivize end-users to charge electric vehicles overnight. The daily load profile is further augmented by high penetrations of photovoltaic (PV) systems, which reduce the midday demand. The resulting load profile exhibits a more flattened characteristic when compared to the historical cyclic profile. Although the initial impact of PV and ES applications may reduce a unit’s peak demand, long-term system planning and emergency conditions may require operation near or above the nameplate rating. Researchers have already determined that a flattened load profile excessively ages a unit’s dielectrics more rapidly. The focus of this research was to identify an approach for establishing new transformer capacity limits for units serving flattened load profiles with a high harmonic content. The analysis utilizes IEEE standards C57.91 and C57.110 to develop an aging model of a 50 MVA SPX Waukesha transformer. The results establish a guideline for determining transformer capacity limits for normal operation, long-term emergency operation, and short-term emergency operation when serving systems with high penetrations of DSM applications.

Publisher

MDPI AG

Subject

Fluid Flow and Transfer Processes,Computer Science Applications,Process Chemistry and Technology,General Engineering,Instrumentation,General Materials Science

Reference50 articles.

1. Power Distribution Planning Reference Book, Second Edition, Revised and Expanded;Willis,2004

2. IEEE Guide for Loading Mineral-oil Immersed Transformers,2012

3. Integrated Energy Storage: An Answer to Addressing the Duck Curve http://www.renewableenergyworld.com/articles/2015/04/integrated-energy-storage-an-answer-to-addressing-the-duck-curve.html

4. What the Duck Curve Tells us about Managing a Green Grid https://www.caiso.com/Documents/FlexibleResourcesHelpRenewables_FastFacts.pdf