AbstractSF6 has been introduced as an insulating and extinguishing gas in gas circuit breakers. However, its global warming potential is significantly high at approximately 25 200. Therefore, development of alternative gases is essential. We have been investigating the dielectric breakdown characteristics of high temperature CO2 gas contaminated by various gases. This study discusses the equivalent condition between high temperature CO2/O2/C5F10O gas mixture and CO2/O2 gas mixture contaminated with PTFE (C2F4) vapor because both gas mixtures consist of C, O, and F atoms. It is concluded that when the mole fractions of every atom are equivalent between both gas mixtures, both gas mixtures have the same characteristics as each other, such as the particle composition and critical electric field strength. © 2023 Institute of Electrical Engineers of Japan. Published by Wiley Periodicals LLC.
Subject
Electrical and Electronic Engineering
Reference16 articles.
1. IPCC.Sixth Assessment Report of Intergovernmental Panel on Climate Charge (AR6). Chapter 7 The Earth's energy budget climate feedbacks and climate sensitivity—Supplementary Material 7SM‐29.
2. ${\rm CO}_{2}$ as an Arc Interruption Medium in Gas Circuit Breakers
3. Fundamental research on SF6‐free gas insulated switchgear adopting CO2 gas and its mixture;Uchii T;Proceedings of International Symposium on Eco Topia Science,2007
4. Approach to Decaying Process of Arc Conductance after Current Zero on the basis of Thermodynamic and Transport Properties of High Temperature Gases
5. Arc Parameters in CO2-blast quenching chamber with high-pressure storage tank of different pressures