Affiliation:
1. EDF Lab Chatou 6 quai Watier 78401 Chatou France
2. Université de Lorraine Laboratoire Réactions et Génie des Procédés, CNRS UMR 7274 1 rue Grandville, BP 20451 54001 Nancy France
Abstract
AbstractIndustrial cooling circuits with wet cooling towers use raw water to remove residual heat from industrial processes. These circuits are very prone to fouling and particularly biofouling. This work proposes a compartmental model built from a full hydrodynamic characterization (using computational fluid dynamics and experimental, local, and system data) of an industrial cooling circuit and implemented with a biofilm growth model which considers kinetic (temperature, concentrations) as well as hydrodynamic (internal and external transfer) limitations. It can therefore predict the biofouling growth per surface unit in the different part of the circuit, considering the various hydrodynamic conditions, while taking only a few minutes to simulate a full year considering season variation of temperature and water quality.
Funder
Association Nationale de la Recherche et de la Technologie
Subject
Industrial and Manufacturing Engineering,General Chemical Engineering,General Chemistry
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献