Influence of the Arrangement of Surgical Light Axes on the Air Environment in Operating Rooms

Author:

Kai Tetsuya1ORCID,Ayagaki Nobuyasu2,Setoguchi Hidekazu3

Affiliation:

1. Anesthesiology and Clinical Research Institute, National Hospital Organization Kyushu Medical Center, Fukuoka 810-8563, Japan

2. Central Uni Co., Ltd., Fukuoka 802-0823, Japan

3. Operating Rooms, Kyushu University Hospital, Fukuoka 812-8582, Japan

Abstract

Purpose. Surgical lights in the operating rooms are typically installed in a single axis in the center of the room or in two axes on both sides of the operating table. In the single-axis installation, the air-conditioning outlet cannot be placed in the center of the ceiling, which may affect the air current. Therefore, we measured the air current and cleanliness in two equivalent operating rooms using a vertical laminar airflow system equipped with either single-axis or double-axis surgical lights. Methods. Air current was measured using a three-dimensional ultrasonic anemometer. Cleanliness was evaluated by measuring the amount of dust before and after air-conditioner activation. To visualize the air current, smoke was illuminated on a sheet of laser light while the air-conditioning was stopped, and changes after air-conditioning activation were observed. Results. In the single-axis room, an oblique fast air current flowing from the surrounding air outlet toward the center was observed, and the flow velocity fluctuated greatly. In the double-axis room, uniform downward laminar airflow was observed. The amount of dust at the center decreased significantly faster in the double-axis room; thus, the cleanliness at the center was higher in the double-axis room. Persistent stagnation of smoke was observed below the single-axis lighting, whereas smoke below the double-axis lighting was immediately dispersed and the air cleared even when surgical lights were in the position for surgery. Conclusion. Uniform vertical laminar airflow was formed and high cleanliness was achieved in the center of the room when the surgical lights were arranged in two axes.

Funder

Kyushu University Hospital

Publisher

Hindawi Limited

Subject

Health Informatics,Biomedical Engineering,Surgery,Biotechnology

Cited by 8 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3