A proposed method for calculating the voltage and current distributions of grounded and isolated networks subjected to line‐to‐ground faults

Author:

Gouda Ossama. E.1,Dein Adel Z. El2,Mbasso Wulfran F.3ORCID,Alharthi Mosleh4,Ghoneim Sherif S. M.4

Affiliation:

1. Department of Electrical Power Faculty of Engineering Cairo University Giza Egypt

2. Department of High Voltage Networks Faculty of Energy Engineering Aswan University Aswan Egypt

3. Laboratory of Technology and Applied Sciences University Institute of Technology University of Douala Douala Cameroon

4. Department of Electrical Engineering College of Engineering Taif University Taif Saudi Arabia

Abstract

AbstractOne crucial objective of this article is to present simplified and accurate approaches to study the current distribution and ground surface potential around the area surrounding an earthed and isolated system in case of a line‐to‐earth fault. The present study is done in the case of uniform and two‐layer soils. Suggested models for calculating the distribution of the earth's surface current density, step, and touch voltages in grounded and isolated systems are presented, discussed, and adapted. The contact and arc resistances of line to ground faulty conductors are considered. Rods and/or grounding grids usually do grounded systems. The impact of both step and touch potentials and current density are investigated in this article. The methods of the calculations are based on the electrical concepts, the charge simulation method, and the imaging procedure for the grounding system. The suggested method can be considered a novel and simple technique for calculating the current distributions of the ground surface during line to ground fault. The results agree with those obtained by others, with the advantage of the proposed algorithm for its ease of application and simplicity. 3‐D dimensions’ contours of the current density and the electric potential on the earth surface around the faulty point are presented in case of homogeneous and two layers’ soil. Finally, this article's novelty is to devise a method for calculating the step and touch potentials and current density around the point of contact of the conductor carrying the electric voltages in the event of faults occurring in the electrical network, whether the network is grounded or isolated. Such faults of electrical networks may cause human hazards.

Funder

Deanship of Scientific Research, King Saud University

Taif University

Publisher

Institution of Engineering and Technology (IET)

Subject

Electrical and Electronic Engineering,Atomic and Molecular Physics, and Optics

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370