DC overvoltage suppression method of wind farm connected via MMC‐HVDC system

Author:

Chen Siying1ORCID,Li Yingbiao1,Li Shun2,Fu Cong2,Chen Yixing2,Miao Lu2,Bao Bo2

Affiliation:

1. State Key Laboratory of Advanced Electromagnetic Technology, School of Electrical and Electronic Engineering Huazhong University of Science and Technology Wuhan China

2. Power Dispatching Control Center of Guangdong Power Grid Co., Ltd. Guangzhou China

Abstract

AbstractA new integration strategy of grid‐forming‐controlled wind farms connected to the bulk power systems through high‐voltage direct current transmission based on the modular multi‐level converter (MMC) is proposed to solve the problem of traditional uncontrollable DC overvoltage during the short circuit faults at the receiving end. However, a new DC overvoltage phenomenon appears after the fault is cleared, and the interaction between the wind farm and sending‐ and receiving‐end MMCs makes the DC overvoltage mechanism more complex; further exploration shows that DC overvoltage during the sending‐end fault recovery stage occurs under the new integration strategy. Therefore, the evolution process and mechanism of the new DC overvoltage are analysed. It is found that affected by the interaction between wind farms and MMCs, the alternate saturation of the integrators in the PI controller of MMCs is the main cause. Based on this understanding, additional controls are proposed to suppress this DC overvoltage during the fault recovery stage. Simulations are carried out on a test with MATLAB/Simulink, and the results verify the efficacy of the proposed methods in suppressing DC overvoltage.

Publisher

Institution of Engineering and Technology (IET)

Reference27 articles.

1. Overcurrent suppression method for multiple wind farms connected to MMC‐HVDC;Yan J.;IEEE Trans. Circuits Syst. II, Exp. Briefs,2022

2. Application and design of resistive SFCL in ±160 kV MMC‐HVDC system;Jiang Z.;IEEE Trans. Appl. Supercond.,2019

3. Negative Sequence Impedance Emulation: A New Perspective and Control

4. Concept and definition of dynamic symmetrical components with time‐varying amplitude and frequency;Li Y.;IEEE Trans. Energy Convers.,2022

5. Generic Model of MMC-VSC-HVDC for Interaction Study With AC Power System