Abstract
Abstract
There are many types of fault location algorithms and one of it is simple impedance based fault location algorithm which is still widely used by power system utilities around the world mainly because of no communication channel exists between local and remote substations. The aim of this research is to study the combination effects of remote in feed current and fault resistance on the accuracy of simple impedance based fault location algorithm which is used to estimate fault location when the transmission line is connected to equivalent Thevenin sources from both ends. Simulation has been carried out using Matlab Simulink software for single line-to-ground fault and line-to-line fault. For each type of fault, fault location and fault resistance were varied for two conditions which were when remote breaker in open and remote breaker in close conditions. From the results, it can be concluded that remote in feed current will add additional error to the error due to the existence of fault resistance when fault resistance not equal to zero.
Subject
General Physics and Astronomy
Cited by
2 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献