Assessment of energy saving and CO2 emission mitigation of low-lift cooling in computer hardware manufacturing industry: A case study in Thailand

Author:

Nizigiyimana J,Chaiwiwatworakul P

Abstract

Abstract Released heat from production process contributes the largest proportion of cooling load in computer hardware manufacturing industry. According to traditional design practice, chiller plant produces chilled water at a temperature of 7°C to treat the entire load from the production process and from the comfort air-conditioning in buildings. However, the heat from the process is solely the sensible component where high-temperature chilled water (e.g., 15°C) can be used for the heat removal, the chillers equipped with low temperature-lift technology thus offer a great opportunity to improve the plant’s cooling performance. Under the critical global warming situation and the need of decarbonizing industry, this paper investigated the energy saving and CO2 emission mitigation potential of the low-lift technology by which the chiller plant of high-temperature chilled water (15°C) is dedicated for the production process cooling, and the traditional chiller plant of the low-temperature chilled water is used to serve the building air-conditioning. The study site was a large factory of computer hardware manufacturing in Thailand. Through detailed energy auditing, the cooling load profile of the production process was established, and it was used to design the low-lift chiller plant. The annual simulation results showed that in our study case the low-lift chiller plant together with variable motor speed control had 31.6% higher cooling performance than the traditional chiller plant. The plant could reduce the energy consumption by 5,550 MWhelec/year. As the CO2 emission of the grid power in Thailand was 0.47 kgCO2/kWh in 2023 and it was expected to reduce to 0.35 kgCO2/kWh in 2050, the CO2 emissions from implementing the low-lift cooling could be reduced by 49,400 TonCO2 over a course of the 20-year project lifetime. The study results encouraged the low-lift cooling technology as a practical energy efficiency measure in computer hardware manufacturing industry. To our knowledge, while past research focused on the low-lift cooling in building air-conditioning, the study was the first potential assessment project of the low-lift cooling as a deep decarbonization technology for the computer hardware manufacturing industry in Thailand.

Publisher

IOP Publishing

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3