Abstract
Abstract
As intelligent power grid construction advances, substation inspection becomes crucial, particularly in identifying meter readings. Existing meter reading methods are mainly based on the relationship between pointer and scale. However, these methods commonly suffer from the issue of over-relying on prior reading information, limiting readings to known meters. Hereby in this paper, we propose a method reaching more accurate and robust performance for meter reading by utilizing the unnoticed scale value. We determine the meter pointer direction with the aid of Hough transform and the pointer distribution. To detect meters from the scene as well as obtain scale values and pointers from the meter dial, we build an object detection network, named Lite-FCOS, whose backbone adopts a fast global context network that is lightweight and is of powerful feature extraction capabilities. For training these, meter dial detection dataset and dial reading information dataset are constructed. Lite-FCOS achieves 94.4 mAP50 and 96.7 mAP50 on the above two datasets with only 4.2 M parameters and 56.2 FPS. The entire pointer meter reading recognition process only spends 52 ms on an RTX 3080Ti with a successful meter reading rate (SMR rate) of 89.6%, which indicates that the proposed method achieves promising accuracy and speed.
Funder
Guangdong Marine Economic Development Project
Key-Area Research and Development Program of Guangdong Province
Subject
Applied Mathematics,Instrumentation,Engineering (miscellaneous)
Cited by
5 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献