Author:
Clark R. P.,Reed P. J.,Seal D. V.,Stephenson M. L.
Abstract
SUMMARYConcentrations of air-borne bacteria and particles have been measured in turbulently ventilated operating theatres in full flow, half flow and zero flow conditions. Increased air-borne challenge produced by human activity and by mechanical cleaning procedures is demonstrated: die-away of this contamination is shown to be related to the ventilation rate. Ventilation can be reduced or turned off at night and during weekends, and cleaning can also be carried out, without increased risk of infection if full flow is restored one hour prior to preparation for surgery. Areas surrounding the theatres should remain at positive pressure with regard to the general hospital environment during low or no flow periods. The implementation of such energy-saving policies will substantially reduce theatre running costs without introducing infection hazards.
Publisher
Cambridge University Press (CUP)
Subject
Public Health, Environmental and Occupational Health,Immunology
Cited by
19 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献