Affiliation:
1. Technical University of Applied Sciences Amberg-Weiden , Hetzenrichter Weg, Germany
Abstract
Abstract
Ventilation technology in German operating rooms is regulated by DIN 1946-4. Since the release of the latest version in 2018, a positioning analysis (worst-case scenario with the largest space requirement) for determining the required protected area in class 1a operating rooms is mandatory. The aim of this investigation was to use typical workflow scenarios to assess existing installations regarding the match of the required and the built size of the protected area. Positioning analyses were carried out together with the on-site staff for various clinical procedures in 2 hospitals to assess the built versus required protected areas. In all cases, the positioning analysis revealed that required protected areas need to be significantly larger than provided by the existing setup. The size of the protected area that is actually required can only be determined by individual positioning analysis. Most existing installations of low turbulence displacement flow systems (TAV) are likely to be too small. The larger protected areas actually require significantly larger rooms in order to maintain proper thermodynamics. Furthermore, significantly higher volumetric flow rates are required. Finally, the current mismatch between actual and necessary protected area would be a possible explanation for the controversial data situation regarding the infection preventive effects of TAV systems.